我们今天能为您提供什么帮助?

How to make PLC Simulator work into a PC doesn't contain Control Expert ?

Steps to configure PLC Simulator:

1- Copy the PLC_Simulator folder from a machine where Control Expert is installed and place it in the virgin machine.
2- Export the registry from the machine where Control Expert is installed, import it in your virgin machine and install it.
Registry
3- Execute sim.exe in the Folder PLC Simulator.
4- PLC Simulator will appear on the taskbar. Right click and choose Options.
PLC simulator icon
5- In the Simulator Panel Options window click on ... next to Starting Application with password and open your .STA project.
Options
6- Click OK and open PLC simulator Panel by double clicking on the PLC Simulator icon on taskbar.
Panel
7- Notice that Run LED is blinking and Simulator is in IDLE state.
8- Click Reset button to put the PLC in Run mode
Panel
9- Important points to remember is that the PLC project must be configured in Simulator mode and also Automatic start in Run must be enabled.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings