Why are the REAL data type variables data not showing correctly in Vijeo Designer when communicating to a M340 PLC?
Issue:
REAL data type variables data not showing correctly in Vijeo Designer when communicating to a M340 PLC.
Product Line:
Vijeo Designer, M340
Resolution:
The REAL data type variables may not show correctly due to word order not set correctly in Vijeo Designer. When the HMI is communicating to an M340 PLC the double word order must be "Low word first". To change the word order, expand the I/O manager in the navigator and double click on the equipment.

Ensure that the Double Word word order is set to "Low word first"

REAL data type variables data not showing correctly in Vijeo Designer when communicating to a M340 PLC.
Product Line:
Vijeo Designer, M340
Resolution:
The REAL data type variables may not show correctly due to word order not set correctly in Vijeo Designer. When the HMI is communicating to an M340 PLC the double word order must be "Low word first". To change the word order, expand the I/O manager in the navigator and double click on the equipment.
Ensure that the Double Word word order is set to "Low word first"
發佈於: 施耐德電機Taiwan


需要協助?
產品選型工具
快速輕鬆地為您的應用找到合適的產品和附件。
取得報價
立即線上提交您的銷售需求,專業團隊將主動聯繫您。
購買地點
輕鬆在您所在地區找到最近的施耐德電機經銷商。
支援中心
在同一位置找到滿足您所有需求的支援資源。