我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Why the display cannot be duplicated with the Multi Display Adapter and HMIGTU open box Win10?
The option "Duplicate these displays" is not available in Windows setting when using Multi Display Adapter with HMIGTU Open Box Win10
popup windows

This article is applicable for the HMIGTU open box Win10 and the Multi Display Adaptor

Root cause
“Intel® Graphics Driver doesn’t support Duplicate Setting with graphics driver for remote connection (DisplayLink® Graphics Driver).
DisplayLink® Graphics Driver is a graphics Driver for remote connection.

Before to follow the procedure to fix the issue, please note that:
  • Recommend to use Mouse and Keyboard.
  • Disable Write Filter Function
  • Product restart is required
  • After the uninstall, MDA setting is required again. Please set by the “MDA Configuration Tool”

First Step: Uninstall Intel® Graphics Driver
1. Open Control Panel – Uninstall a Program
2. Select “Intel® Graphics Driver” and “Uninstall”
uninstall driver1

3. Open Device Manager
4. Select and Right-Click  “Display adapters – Intel® HD Graphics”
5. Select “Uninstall device”
6. Turn on the check box “Delete the driver software for this device” and select Uninstall

driver issue 2



Limitation:
1. Graphic function performance is down
-> Graphic performance might get slow. Especially animation, video image could be stop (not re-start).

2. The resolution setting of 4:3 Display Model is limited
-> Some resolution could not select. (The recommended resolution for unit is still supported.)

3. The resolution setting and display image of Wide Display Model is not correct
-> Wide resolution might be able to be selected when duplicated. But display image might not be displayed correctly. Display image is stretched or shrunk.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings