我们今天能为您提供什么帮助?

How can we rename a Recipe at Runtime on an HMI?

Issue: Is it possible to rename a recipe that is created during runtime in Vijeo Designer?

Product Line: Vijeo Designer, HMI, Magelis, Harmony

Resolution:

The user can certainly rename the recipes that are created after the "Create New" button is pressed to generate a new recipe at Runtime. There is a setting that you need to set to "True" first in your application before you can start renaming recipes on an HMI during Runtime.

The setting is found in the Recipe Toolchest parts:

The setting is called "RecipeNameEditable"

When this setting is set to True, you will be able to Edit the loaded recipe name. Keep in mind that you will need a "Save" button handy to save any changes.

The order of operations will be like this:

1) Create a new recipe by pressing the "Create New" Button

2) Click on the current recipe name (probably r#)

3) Enter the name for the recipe using the keyboard

4) Press Save.

This will let you customize the recipe names.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings