What is the scale of the Altivar Process Drive Analog output AQ1 when assigned as motor Frequency?
Issue:
Need to know the scale of the ATV600 and ATV900 Drives Analog output AQ1 when assigned as motor frequency.
Product Line:
Altivar Process ATV630 ATV650 ATV930 ATV950
Environment:
All
Cause:
Need to know how the analog output correlates to motor frequency.
Resolution:
The default scale is 0 - tFr (Max Frequency).
Note that the drive's High Speed Setting (HSP) may be same or different.
Example:
ATV630 has HSP = 50Hz and tFr = 60Hz.
AQ1 assigned as 4-20mA output for motor frequency.
motor frequency at 0Hz = 4mA output
motor frequency at 60Hz = 20mA output
It is a linear relationship between these endpoints.
The scaling can be changed with parameters ASL1 and ASH1. See the Programming Manual for details.
Need to know the scale of the ATV600 and ATV900 Drives Analog output AQ1 when assigned as motor frequency.
Product Line:
Altivar Process ATV630 ATV650 ATV930 ATV950
Environment:
All
Cause:
Need to know how the analog output correlates to motor frequency.
Resolution:
The default scale is 0 - tFr (Max Frequency).
Note that the drive's High Speed Setting (HSP) may be same or different.
Example:
ATV630 has HSP = 50Hz and tFr = 60Hz.
AQ1 assigned as 4-20mA output for motor frequency.
motor frequency at 0Hz = 4mA output
motor frequency at 60Hz = 20mA output
It is a linear relationship between these endpoints.
The scaling can be changed with parameters ASL1 and ASH1. See the Programming Manual for details.
發佈於: 施耐德電機Taiwan








需要協助?
產品選型工具
快速輕鬆地為您的應用找到合適的產品和附件。
取得報價
立即線上提交您的銷售需求,專業團隊將主動聯繫您。
購買地點
輕鬆在您所在地區找到最近的施耐德電機經銷商。
支援中心
在同一位置找到滿足您所有需求的支援資源。