我们今天能为您提供什么帮助?

How to Safely Distribute Database Folders to Another Disk/Location in Geo SCADA/ClearSCADA.

⚠️*Warning: This article contains information about editing the registry. Improper changes to the registry can permanently damage the operating system.
Always backup the registry before making any changes.*


In some cases, you may need to distribute Geo SCADA database folders (such as Config, Data, History, etc.) to different disks or locations for performance optimization or storage management. This can be achieved using the Registry Editor method. Below is a step-by-step guide.

Steps to Move Database Folders

Step 1: Shut Down the Geo SCADA Server

  • Right-click the Geo SCADA Server icon in the system tray.
  • Select Shutdown Server.


server shut down

Step 2: Locate the Original Database Folder

  • Navigate to the default database path:
    C:\ProgramData\Schneider Electric\ClearSCADA\Database
    Here you will find folders such as:
  • Config
  • ConfigChanges
  • Data
  • DataFiles
  • HisFiles
  • History
  • Journal
locate folder

Step 3: Move the Desired Folder

  • Copy or move the folder you want to relocate (e.g., ConfigChanges, History) to the new disk or location.

Step 4: Update the Registry

  • Open Registry Editor (regedit).
  • Navigate to:
    HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\ClearSCADA\DB
  • Locate the registry key corresponding to the folder you moved (e.g., ConfigChangePath, HistoryPath).
  • Update the Value data to the new folder path.

regitry

Step 5: Restart Geo SCADA Server

  • Start the Geo SCADA server again.
  • Verify the new folder location in Server Configuration → System configuration → Location.

server config

Best Practices

  • Ensure the new location has sufficient disk space and proper permissions.
  • Avoid moving folders while the server is running.
  • Keep a backup of the original database before making changes.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings