How do I update the firmware of my SRTG 15 & 20kVA UPS?

Issue:

SRTG 15 & 20kVA UPS requires a firmware update.

Product Line:

Smart-UPS models SRTG15KXLI and SRTG20KXLI

Environment:

  • Computer with Windows 7 or Windows 10 operating system
  • The USB A to USB B type communication cable supplied with the UPS
  • "UPS-UpdateToolInstaller.zip" file - available at the end of this document
  • "15-20k V1.19 20220909.zip" Firmware File - available at the end of this document


Resolution:

NOTE: The UPS system is expected to power down during the firmware upgrade. It is recommended to turn off the load connected to the UPS before starting the firmware upgrade.

Preparation:

  1. Connect the USB A to USB B type communication cable supplied with the UPS cable between the UPS and computer.
    • 1
  2. Download the "UPS-UpdateToolInstaller.zip" and "15-20k V1.19 20220909.zip" files attached at the end of this document.
  3. Extract the "UPS-UpdateToolInstaller.zip" file.


Installing the Update Tool:

Double click the "UPS-UpdateToolInstaller.exe" file to start installing the update tool.

  1. Select OK.
    • 2
  2. Select Next.
    • 3
  3. Select Install.
    • 4
  4. Ensure that the "Launch UPS-UpdateTool" option is selected, and then select Finish. This will launch the update tool.
    • 5


Updating the UPS Firmware:

  1. Select the language: English.
    • 6
  2. Select the appropriate port number where the USB cable is connected to the computer.
    • 7
  3. Press "select" and browse to the location where the "15-20k V1.19 20220909.zip" file was downloaded in Preparation Step 2.
    • 8
    • 9
  4. Ensure both check boxes are ticked:
    • 10
  5. Select Updating:
    • 11
  6. The update may take 15-20 minutes. Once the update is completed, the update tool can be closed:
    • 12

Verifying the firmware version

Use the UPS front panel to navigate to the following menus.

  1. Press the OK key to enter the Main Menu, press the ▼ key to select Configuration and press the OK key to enter the submenu.
    • 13
  2. Press the ▼ key to select Display, and click OK to enter the submenu.
    • 14
  3. Press the ▼ key to select the Menu Type, and click OK to enter the menu type selection screen.
    • 15
  4. Press ▼ key to select Advanced, and press OK to confirm.
    • 16
  5. Press ESC key until you return to the Main Menu.
  6. In the Main Menu, press the ▼ key to select About, click OK to enter the submenu.
    • 17
  7. Select UPS and click OK to enter the submenu.
    • ​​​​​​​18
  8. Press the ▼ key to view firmware component versions.
    • ​​​​​​​​​​​​​​19 ​​​​​​​

施耐德電機Taiwan

附件
UPS-UpdateToolInstaller.zip [10.77 MB]
15-20k V1.19 20220909.zip [301.17 KB]
探索更多
產品:
探索更多
產品:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings