How to Discover and Add Modbus Serial and Modbus TCP Devices to EcoStruxure™ Panel Server Using EcoStruxure™ Power Commission

EcoStruxure™ Power Commission provides a structured discovery workflow to identify and add Modbus TCP and Modbus serial devices connected to an EcoStruxure™ Panel Server. Discovery can be performed either directly via IP network scanning or through the Panel Server gateway.
To begin, open EcoStruxure™ Power Commission and select Launch Device Discovery. In the IP / Ethernet tab, enter the IP address of the EcoStruxure™ Panel Server. If Modbus serial devices are connected behind the panel server, specify the Modbus address range and click Next. EPC will scan the panel server and display a list of all detected Modbus devices along with their respective addresses. Select the required devices and click Add Devices to include them in the project.
Alternatively, the Panel Server can be added to the project first by entering only its IP address. Once the device is discovered and connected, select the Modbus Devices card. The system prompts whether to add the Modbus devices connected to the gateway. Selecting "Yes" automatically adds all detected Modbus TCP and serial devices into the project.
After successful addition, all Modbus devices are visible in the Switchboard View, organized within the switchboard hierarchy, such as power meters, circuit breakers, and other connected equipment.
Refer to the added document to see how the devices are added in Ecostruxure Power Commission.

Troubleshooting and Common Errors

1. No Devices Discovered During Scan

  • Verify that the EcoStruxure™ Panel Server is powered ON and reachable on the network.
  • Confirm the correct IP address is entered in EcoStruxure™ Power Commission.
  • Ensure the PC running EPC is on the same subnet as the panel server.

2. Modbus Devices Not Listed After Panel Server Connection

  • Check that Modbus serial devices are correctly wired to the panel server.
  • Validate the configured Modbus addresses and ensure there are no address conflicts.
  • Confirm that the Modbus communication parameters (baud rate, parity, stop bits) match the device configuration.

3. Manual Discovery Fails to Find Devices

  • Ensure the correct Modbus address range is entered during manual discovery.
  • Verify that the devices are supported by EcoStruxure™ Power Commission.
  • Check that Modbus TCP devices are enabled for IP discovery on the network.

4. Devices Appear Offline After Addition

  • Verify network stability and Ethernet cabling.
  • Confirm the panel server firmware and EPC version compatibility.
  • Restart the Panel Server and re‑establish the connection from EPC if required

施耐德電機Taiwan

附件
Discover & Add Modbus, TCP device to EcoStruxure Panel Server.pdf [2.29 MB]

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings