我们今天能为您提供什么帮助?

What items are included in the package of the Back UPS BVG series?

Issue:

What items are included in the package of the Back UPS BVG series?

Product Line:

Back-UPS Models BVG series.

Environment:

All serial numbers



Resolution :

 

The packaging contents of the APC Back-UPS BVG series typically include the following items:

  1. Back-UPS BVG unit – The main uninterruptible power supply device.
  2. Safety guide and quick Installation guide – Instructions for setup and safety information.

See screenshot below:

BVG series Packaging content

packaging content


施耐德電機Taiwan

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings