我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
EcoStruxure Power Operation: How to expose the custom trend tag in ETL so that it will extract trend data from EPO and load it in PME SQL DB or in other file formats?

Issue

From ETL v6.2 I am unable to extract the EPO/PSO custom tag historical trend data using ETL tool.

Environment

Power SCADA Operation (PSO) 2020 With ETL v6.2

EcoStruxure Power Operation (EPO) v2021 / v2022 With ETL v6.2

Cause

This is a known issue prior to ETL v6.2. However, from this version for custom tags we need additional configuration which is explained in Resolution section.

Resolution

When configuring ETL Job > PSO Extract task make sure to set Include Custom Topics In Mapping Operations = True
ETL_1

After this follow the normal process to configure remaining part of task. Above step will help ETL tool to load the custom tags while Loading Sources in “Mappings” tab of the tool.
But to extract historical trend data from EPO DB, then you may need to create the custom Topics.xml file as per below screen cap (also sample file attached with this article) and place it in ETL install folder [the default location ‘C:\Program Files\Schneider Electric\ETL (PowerSCADA)’] and configure all the custom tags as per below example.
ETL_2
Note:LegacyTopicID must be unique negative number.
Have a look in to attached example Topics.xml file for more info.

施耐德電機Taiwan

附件
Topics_Example1.xml [1.67 KB]
Topics_Example2.xml [2.56 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings