我们今天能为您提供什么帮助?

How to Restore a corrupted VIP in Power Monitoring Expert

Issue:
VIP has been deleted or corrupted. The designer has unassociated modules from their programs and groups them by module type rather than defined grouping objects, i.e., "Arithmetic Modules", "Data Recorder Modules", etc.

Product Line:
Power Monitoring Expert 7.2.2
Power Monitoring Expert 8.2
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment:
Designer
Diagnostics Tool

Cause:
This can happen when a VIP configuration file has become damaged, corrupted, or unassociated with the folder it is inside. This can happen as a result of incorrectly changing the VIP folder name by changing the folder name in File Explorer.

Resolution:
VIP backup files are taken with each diagnostic. Navigate to a previously taken diagnostic and restore the files with the following process.

Note: This will only work to restore the VIP to a previous backup taken from the Diagnostics file.
  • Navigate to a previous Diagnostics cab file. Unzip. Diagnostics File -> Outputs -> VIP files.
  • Copy vip."name".bak, vip."name".cfg and vip."name".nd.cfg.
  • Stop all ION services.
  • Navigate to ...Schneider Electric\Power Monitoring Expert\config\cfg\vip. Copy the vip.cfg and vip.bak files associated with the VIP you want to restore. Store them in a safe location.
  • Delete the vip.bak and vip.cfg from the folder.
  • Navigate to ...Schneider Electric\Power Monitoring Expert\config\diagrams\nd. Copy the vip.cfg. Store in a safe location.
  • Delete the vip.cfg from the folder.
  • Copy the old vip.cfg and vip.bak files into the associated VIP folder. Rename to match naming convention. "vip.cfg" and "vip.bak"
  • Copy the old diagram vip.cfg into the associated diagram folder. Rename to match naming convention. "vip.'vipname'.cfg".
  • Restart all services.
  • Verify program has returned to its previous state in Designer.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings