我们今天能为您提供什么帮助?

Why does my UPS report erroneous bypass alarms on the NMC web interface?

Issue: The UPS may report erroneous bypass alarms on the NMC web interface, even if the UPS does not have a bypass feature or it is not actually transferring in or out of bypass operation mode.

Examples of alarms reported:
"Device   UPS: Return from bypass, internal hardware fault no longer present.        0x01B2"
"Device   UPS: In bypass in response to an internal hardware fault.              0x011B"

Product Line: Smart-UPS with Network Management Card (NMC) 3

Environment: Network Management Card firmware version 2.2.0.1

Resolution: This issue has been addressed in NMC3 firmware version 2.2.1.1. Please update the firmware of your NMC3 to the latest version.

The latest NMC3 firmware is available on apc.com. Refer to the below example on how to find and download the NMC3 firmware, and to FA156047 for instructions on upgrading the NMC3 firmware.

download from web

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings