How to restrict OFS-DCOM connection to a specific user?

OFS Server can operate in remote mode (the OPC client and the server are on different machines connected by DCOM generally via TCP-IP)

To allow the connection for only a specific user, the following setting can be applied:

Steps to follow:

  • From the Start menu, choose Run and run DCOMCNFG
  • Expand Console Root/Component Services/Computers/My Computer and
  • right-click My computer to open the My Computer Properties dialog.
  • Click the Default Properties tab.
  • The following parameters must be set:
    • Enable Distributed Com on this computer must be checked,
    • Default Authentication Level is set to Connect,
    • Default Impersonation Level is set to Identify.

dcom

  • Click the COM Security tab.
  • Click the Edit Defaults in Access Permissions
  • Click Add, add the user required (example: L3), click OK.
  • Check that permissions for user required are:
    • Local access: Allow checked.
    • Remote access: Allow checked

dcom

  • Delete « Everyone » if it exists
  • Delete « INTERACTIVE » and « NETWORK » if it exists
  • Click the Edit Defaults in Launch and Activation Permissions
  • Click Add, add the user required (example: L3), click OK.
  • Check that permissions for user required are:
    • Local Launch: Allow checked.
    • Remote Launch: Allow checked.
    • Local Activation: Allow checked.
    • Remote Activation: Allow checked.

dcom

  • Delete « Everyone » if it exists
  • Delete « INTERACTIVE » and « NETWORK » if it exists

Product line

OFS 3.63 SP3

Environment

Windows 10

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings