我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
RemoteConnect Configuration Log - Invalid Field ID

I wrote a configuration to a SCADAPack 474 while online with the controller and received the following Invalid Field errors in my Configuration Log.

This typically occurs when RemoteConnect is attempting to configure functionality that the firmware does not have.  This results in some intended functionality not being applied.

Configuration Log details below:

#Rebuilding Configuration from file configuration.rtu at 13:31:37 on 16-05-2024

File Attributes: 103799 bytes, 13:31:36 16/05/2024

File is valid. Rebuilding Configuration

# 7448: Invalid field Id: 354073

# 7496: Invalid field Id: 150901

# 7558: Invalid attribute for point: 551210

Configuration Rebuild Pass

To correct this issue apply the firmware bundled with the version of RemoteConnect that you're using.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings