我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to Link a VIM (Voltage Interface Module) to one of our Avatars Loads in TeSys Island

Product Line:
Industrial Automation Control

Environment:
Motor Management Systems  TeSys Island

Cause:
What´s the correct path to add a Voltage Interface Module on of my avatar Loads

Resolution:

Voltage Interface Modules will require to be added to a specific Load Avatar in order to be mapped on the TeSys Island topology, to add this module, the correct path will be to first add our Load , it can be a standard starter or a SIL starter:

We will need to add a LOAD to My Avatar

Add Avatar TeSys Island

To load our VIM we will need to add the Load Energy Monitoring in our Avatar Parameters window

Load Energy Monitoring TeSys Island

This will automatically add the Voltage Interface Module to our LOAD and will be added to the Avatar Topology:

Physical View TeSys Island

施耐德電機Taiwan

探索更多
產品:
系列:
探索更多
產品:
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings