我们今天能为您提供什么帮助?

How to generate a General Interrogation with report control block by using BMENOP0300 ?

The BMENOP0300 can be used in report mode. In this conditions, the BMENOP0300 is receiving reports coming from the IED device where report has been enabled.

In some conditions, a General Interrogation can be performed. This GI need to be generated by changing some options inside the report control block.

We would suggest to Performed the GI (General Interrogation) once only with the following condition:

1) We can get the good health status of the individual IED

2) We can get the good Data freshness status of the individual IED.

3) We managed to enable the Report control block with the positive response from the particular IED.

4) If all the above conditions are met then we are ready to give a GI using the report control block.

5) In order to give the GI as mentioned earlier all the condition should be met, means in IED reports is already enabled.

6) Using the Report control block and set 11 (decimal) in the options of the report block.

 Report control block and set 11

7) Change the value in CMD of the report block to trigger the GI.

CMD of the report block to trigger the GI

8) Monitor the status feedback of the GI.

 status feedback of the GI.

In a wireshark trace, you can see the GI emission from the BMENOP0300.

wireshark trace

9) This is how the GI is performed.

Product Line

BMENOP0300

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings