PME 2024- Tamper detected error. A valid software license could not be found.

Product Line
Power Monitoring Expert 2024
_____________________________________________________________
Environment
License Configuration Tool
_____________________________________________________________
Issue :
A valid software license could not be found.
A valid license could not be found

The system logs are flooded with the error: Tamper detected: FlxDotNetClient.SvcSessionException: MID=0, SID=0, EID=6

_____________________________________________________________
Proposed Solution

Solution 1:

Import the attached certificates into the Trusted Root Certification Authority through the Manage Computer Certificates interface.

  1. VeriSign Universal Root Certification Authority.cer
  2. VeriSign Class 3 Public Primary Certification Authority - G5.cer
  3. DigiCert Trusted Root G4.cer
    Trusted Root Certification

    Then Run the below PowerShell script after getting the exported certificate in the system.

    Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode.

    $sst = ( Get-ChildItem -Path C:\certs\roots.sst )

    $sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

    Solution 2:
    If the previous solution fails, rebuild the certificate chain from a functioning PME system.
    From a working PME system, export the three previously stated certificates.
    Here is the link to exporting the trusted root certificate from the working machine.
    http://woshub.com/updating-trusted-root-certificates-in-windows-10/

    Then run the below PowerShell script in the non-working system after getting the exported certificate in the system:

    Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode

    $sst = ( Get-ChildItem -Path C:\certs\roots.sst )

    $sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

施耐德電機Taiwan

附件
VeriSign Universal Root Certification Authority.cer [1.18 KB]
VeriSign Class 3 Public Primary Certification Authority - G5.cer [1.21 KB]
DigiCert Trusted Root G4.cer [1.39 KB]

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings