我们今天能为您提供什么帮助?

IDP10-T/IGP10-T Calibrate at Known Tank Level

X = Actual value to be displayed

Y = Original M1 LRV value

  1. Press the NEXT button and the word RERANGE will be displayed.
  2. Press ENTER and M1URV will be displayed
  3. Press NEXT and M1LRV will be displayed
  4. Make note of this value as the “Y” value
  5. Press ENTER and left hand most digit will blink. Press NEXT until this digit is equal to the most significant digit of the “X” value
  6. Press ENTER and the next digit will flash
  7. Press NEXT until this digit matches the value of the next most significant digit of the X value. Repeat procedure for the remaining digits until the entire X value has been entered
  8. Press ENTER and Place DP will be displayed
  9. Press NEXT until the decimal point is in the correct location
  10. Press ENTER and CANCEL will be displayed
  11. Press NEXT and SAVE will be displayed
  12. Press ENTER and device will be returned to Measurement Display
  13. Press the NEXT button 3 times and CALIB will be displayed
  14. Press ENTER and display will indicate CAL AT0
  15. Press next and display will indicate CAL LRV
  16. Press the ENTER button and display will indicate CAL WAIT and then display LRVdone
  17. Press NEXT 6 times and SAVE will be displayed
  18. Press Enter
  19. Press the NEXT button and the word RERANGE will be displayed.
  20. Press ENTER and M1URV will be displayed
  21. Press NEXT and M1LRV will be displayed
  22. Press ENTER and left hand most digit will blink. Press NEXT until this digit is equal to the most significant digit of the “Y” value
  23. Press ENTER and the next digit will flash
  24. Press NEXT until this digit matches the value of the next most significant digit of the Y value. Repeat procedure for the remaining digits until the entire Y value has been entered
  25. Press ENTER and Place DP will be displayed
  26. Press NEXT until the decimal point is in the correct location
  27. Press ENTER and CANCEL will be displayed
  28. Press NEXT twiceand SAVE will be displayed
  29. Press ENTER and device will be returned to Measurement Display
  30. Complete

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings