我们今天能为您提供什么帮助?

How to view the real time logic address of Altivar Drives?

Issue:

How to view the real time register or bits within these Input and Output Scanner Modbus Registers?

Product Line:

ATV630, ATV930, ATV340

Environment:

All serial numbers

Cause:

This has to do with troubleshooting capabilities.

Resolution:

In SoMove, there are three options to see the values of registers.

1) Under Display -> Communication Mappings

SoMove_1

2) The second option is to create your own display by clicking on "Motor" and "Drive" then highlight and pull the registers to the empty space to create your own display.

SoMove_2

The third option is to add the parameter for visualization on Dashboard/Display section, by its Logical Address - example is LFRD:

SoMove_3

For legacy drives like ATV61/71/320 - the feature in SoMove is not available.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings