How to retrieve log files from a controller in EAE BT

1.Open EAE Buildtime and load the EAE Solution currently running on your controller.

2. Navigate to the Deploy & Diagnostics tab.

3. Log in to the device.

4. Expand the Action tab for your controller, then go to Log File > Fetch log files to retrieve the files.

M580d fetch log

5. Wait for the message: "Fetching of log file successfully finished."

action progress

6. Close the Device Log Viewer pop-up window.

7. Locate the cyclic.log and device.log files in the following path (also see note c. below)
Documents\Schneider Electric\EcoStruxureAutomationExpertProjects\<project_folder(s)>\IEC61499\Log

8. Send both files to Technical Support.

NOTES:

a. This Knowledge Article was made based on EAE version 24.1.

b. For SoftdPAC HA configurations, log files should be fetched from the parent controller menu to ensure that the cyclic and device logs for both the left and right iPCs are retrieved. Make sure to send all four files to Technical Support.

HA fetch log

c.  The path to retrieve the log files from your controller can also be retrieved from the Device Log Viewer pop-up window, by:

  • Clicking on File > Load Log
  • In the Open Log file window, right click on the folder address and click on Copy address as text

retrieve path

  • Open a File Explorer window, edit address and paste the one retrieved from the Log window. Press ENTER.

file explorer

施耐德電機Taiwan

探索更多
產品:
系列:
探索更多
產品:
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings