我们今天能为您提供什么帮助?

How to Migrate PME to a New Database Server

Issue

Migrating PME to a new database server.

Product Line

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

Power Monitoring Expert

SQL Server

Resolution

  1. Confirm SQL server instance is compatible with the PME version by checking the corresponding system guide underneath Operating Environment. The link here will take you to the PME 2024 compatibility list: Operating Environment
  2. Follow the directions for a SBS upgrade for distributed systems. Ignore step 8. Step 2 - Transfer the Configuration
  3. Now that an archive has been taken, a system key has been generated and the databases have been transferred, the old version of PME must be uninstalled. Follow the instructions in the article "How to uninstall Power Monitoring Expert (PME) | Schneider Electric USA ". Do NOT skip steps as a clean uninstall is crucial to a successful migration.
  4. Install the new version of PME as a distributed system, pointing to the new database server. Installing the PME software
  5. After successful installation, detach and delete the freshly installed databases. Restore the old database backups.
  6. Open the CMTool, Load from Archive, and Write to System. Resolve any errors that you encounter.
  7. After a successful write to system, reconfigure the PME system.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings