我们今天能为您提供什么帮助?

How to Configure Secure Services (HTTPS, SSH, and RADIUS) on SAGE RTU

Title:

How to Configure Secure Services (HTTPS, SSH, and RADIUS) on SAGE RTU

Issue:

Need to enable secure communication and centralized authentication on SAGE RTU for compliance and cybersecurity.

Product:

SAGE Remote Terminal Unit (RTU) All models

Environment:

  • Firmware version C3414-500-S02YZ or later
  • Config@WEB GUI accessible via HTTPS
  • User Manager and Configuration Converter tools installed on PC (.NET Framework 3.5+)

Cause:

Default configuration may allow insecure protocols (HTTP, Telnet, FTP). Secure services must be enabled to meet security standards and prevent unauthorized access.

Resolution:

1.- Enable Secure Services via GUI:

  • Navigate to CPU Configuration → Services Setup.
  • Select the following options for maximum security:
      • HTTPS (Port 443) for encrypted web access
      • SSH Server (Port 22) for secure remote shell
      • SFTP for secure file transfer
      • Enable Remote Shell for VxWorks shell access
      • IPsec for VPN traffic encryption
      • Enable RADIUS Authentication for centralized user management

2.- Configure RADIUS Authentication:

  • Enable RADIUS client in CPU Configuration.
    • Click Configure Servers and enter:
      • IP Address of RADIUS server
      • UDP Port (default 1812)
      • Retries and Timeout values
      • Shared Secret (must match on RTU and RADIUS server)
  • Up to 5 RADIUS servers can be configured.

3.- Generate and Install Keys:

  • SSH: Generate DSA/RSA keys for RTU and users; include in user package via User Manager.
  • HTTPS: Replace default SSL key and certificate using Configuration Converter; generate custom files externally.

4.-Apply Changes:

  • Upload updated configuration via GUI Up/Download tab.
  • Perform RTU reset for changes to take effect.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings