我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Geo SCADA Upgrade Issue: Wonderware Alarm Provider Service Stuck During Installation

When upgrading EcoStruxure Geo SCADA Expert, the installation process may fail because the Wonderware Alarm Provider service cannot stop. This service often gets stuck in a “Starting” state, preventing the installer from proceeding.

The installer displays the following error message:

Service 'Geo SCADA Expert Wonderware Alarm Provider' (WWAPSERVICE) could not be stopped.
Verify that you have sufficient privileges to stop system services.

installation error

In Services, the Geo SCADA Expert Wonderware Alarm Provider status is stuck in Starting and does not respond to stop commands.

service stuck

Workaround to Resolve the Issue:

Step 1: Disable the Service

  1. Open Services.
  2. Locate Geo SCADA Expert Wonderware Alarm Provider.
  3. Right-click the service → Properties.
  4. Set Startup type to Disabled.
  5. Click Apply and OK.

Step 2: Reboot the System

Restart the computer to clear the stuck state and prevent the service from starting automatically.

Step 3: Rerun the Installer

After reboot:

  • Launch the Geo SCADA installer again.
  • The installation should proceed without the previous error.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings