我们今天能为您提供什么帮助?

What can I do in the “Manage Projects” section.?

Once logged in, the user can use all of the below features.

    • Create a new project.
    • Load a previously created project.
    • Get access for All Project, My projects.
    • Can use Share via link, Duplicate, Export as file, Delete for the created projects.
  1. Get access for All Project.
    1. Click All Project to see the page.
    2. This page shows all the projects available in your account.
  2. Get access for My projects.
    1. Click My projects to see the page
    2. This page shows all the projects created by you in your account.

NOTE: User need to login to access this feature.

Manage the Projects
Projects page

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings