How do you untag ports on a Modicon Switch when working with PRP configuration files?

The PRP configuration files set all ports on the MCSESM switch to VLAN 1. This ensures communication between the M580 CPU and the BMECRA31310 module, but this also means that only devices supporting VLAN 1 can be connected directly to the switch.

However, some customers may need a dedicated port for:

  • Troubleshooting
  • Connecting DIO or other devices that do not support VLAN tagging

In these cases, you can manually configure a port as untagged, by following one of the two steps below.

Modicon Switch Configuration Web Page

  1. Log in to the MCSESM web interface
    1. Default username: Admin
    2. Default password: private
  2. Search for VLAN Configuration in the configuration file text box.
  3. Locate the port you want to modify.
  4. Change the port setting from T (Tagged)U (Untagged).
  5. Click the check mark to confirm the change.
  6. Click Save Configuration.

image1

PRP Configuration File

  1. Open the MCSESM PRP pre‑configuration file using Notepad or Notepad++.
  2. Navigate to the section for the port you want to modify.
    1. Ports are listed using the format 1/#, for example:
      1. Port 1 → 1/1
      2. Port 5 → 1/5
      3. Port 10 → 1/10
  3. Change the assignment from VLAN tagging 1 to no VLAN tagging 1.
  4. Save the file.
  5. Upload the updated configuration file to the MCSESM switch.

image2

For more information regarding how to upload files to the MCSESM switch, please reference Modicon M580 Redundant Communication Adapter Module (PRP) for X80 RIO Drops Installation and Configuration Guide, starting on page 41.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings