我们今天能为您提供什么帮助?

PowerChute Network Shutdown fails to power down ESXi host and records in the error log "cannot obtain HostSystem using findByIP or findByDnsName for critical host:"

Issue:

PowerChute error log reports "cannot obtain HostSystem using findByIP or findByDnsName for critical host:" for the configured ESXi host listed in the host protection page, and the host fails to power down.

Product:

PowerChute Network Shutdown

Environment:

PowerChute configured with VMware vCenter Server

Cause:

This concerns how the host's name appears in the vCenter inventory.

Example: The vCenter inventory lists the host as apc-esxi01.somedomain.com , while on the ESXi host, the hostname appears as ABC-ESXI01. This mismatch causes the FindByDNSName API call to fail when issued against an ESXi host.

Solution:

Log in to each ESXi host via SSH and use esxcli to update the hostname to match what appears in vCenter:

esxcli system hostname set --fqdn apc-esxi01.somedomain.com

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings