Ecostruxure Process Expert for ASP [2023]: How to resolve ASP-Asset Link configuration not able to generate instances.

This Knowledge Base article helps users who encounter issues in a new setup project when attempting to generate object instances in ASP using the Asset Link configuration.

During project development, the following behaviors may be observed:
  • The system fails to generate object instances in ASP from the Asset Link configuration.
  • No error dialog, warning, or notification is shown to the user.
  • The corresponding XML file is generated, but not in the correct format.
  • Specifically, the Local/Area attribute values in the XML output are missing, appearing as empty or null fields.
  • Because these critical attributes are absent, the ASP engine silently skips instance generation.

Refer below image details for more information,

Error XML format

The issue occurs in the Control Project when the Auto Assign Candidate Facets setting is disabled. Refer below image details for more information,

PE settings details

Based on the current product design, instance information is retrieved from the container only when this flag is enabled. Since the flag is set to false (Disable) , an empty instance list is passed to the Export Plant Model Hierarchy process. As a result, the generated XML does not include the expected hierarchical details.

To resolve this instances not generated behavior issue, user need to be modified above mentioned settings from disable to Enable.

This Issue is noted in EPEFASP2023 version. But its applicable to all the versions of Ecostruxure Process Expert Aveva System Platform.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings