我们今天能为您提供什么帮助?

Reports Time Out In PME Web Apps

Issue

When running reports, the report will timeout with an error:

"An error occurred while attempting to retrieve the data."

Errors

Product Line

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

Web Applications Reports

Management Console

Cause

Report querying is dependent on multiple factors (number of source measurement pairs, resources available to SQL, number of simultaneous sessions, etc). Some reports may require additional time than the standard 5 minutes.


Resolution 1

  1. Navigate to Management Console -> Tools -> Reports Configuration.
  2. Increase timeout seconds.

Report Subscription

**Note that increasing timeout may cause reduced performance**

Resolution 2

Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.

If the above does not work, the following locations can be edited to increase timeout.

SELECT TOP (1000) [Module]

,[Category]

,[Item]

,[Value]

,[DefaultValue]

FROM [ION_Network].[dbo].[vCFG_ConfigItems]

where item like '%timeout%'

Reports

Setting a maximum time of 1800 seconds (30 mins) for these fields may allow the report to complete. Please contact support prior to making these changes.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings