Meaning of PD2 Marking on Current Transformers
Issue
Customers question the meaning and implications of the PD2 marking found on CT labels, such as the “PD2” indication shown on some Schneider Electric split‑core and solid‑core CT models.
Product
Current Transformers (CTs), including but not limited to:
- Split‑core CTs (e.g., METSECTSP series)
- Solid‑core CTs used with Schneider Electric energy meters and monitoring equipment
Environment
Electrical distribution systems where CTs are installed in:
- Indoor electrical panels
- Industrial or commercial facilities
- Enclosures with normal environmental conditions (non‑corrosive, non‑conductive dust)
Cause
The PD2 marking refers to Pollution Degree 2, a classification defined by IEC/UL insulation standards. This marking indicates the expected level of environmental contamination around the equipment.
According to IEC 60664‑1 and UL 61010 standards, Pollution Degree 2 means:
- Only non‑conductive contamination is normally present.
- Temporary conductivity may occur only due to condensation.
Resolution
The PD2 marking It simply informs users that the CT is designed and safety‑rated for installation in environments meeting Pollution Degree 2 conditions.
Recommended actions:
- Verify installation environment: Ensure the CT is mounted inside an enclosure or panel that meets PD2 environmental characteristics.
- Avoid excessive dust, humidity, or corrosive atmospheres: If the environment exceeds PD2 (e.g., heavy industrial dust, chemical vapors, persistent moisture), consider additional enclosure protection or relocating equipment.
- No technical intervention is required unless the CT is being installed in a harsher‑than‑rated environment.
Example:
發佈於: 施耐德電機Taiwan
需要協助?
產品選型工具
快速輕鬆地為您的應用找到合適的產品和附件。
取得報價
立即線上提交您的銷售需求,專業團隊將主動聯繫您。
購買地點
輕鬆在您所在地區找到最近的施耐德電機經銷商。
支援中心
在同一位置找到滿足您所有需求的支援資源。