Ecostruxure Process Expert for ASP [2023]: How to Resolve Asset Link 4.0 SP1 License detection Issues in ASP

This Knowledge Base article assists users who encounter an issue in a new system setup project where Asset Link fails to detect a valid license, causing the system to operate in trial mode instead of licensed mode.

When this issue occurs, Asset Link does not connect to the license server, and ASP runs with limited functionality.

Refer to the image below for more information:

Trail_mode

This issue typically occurs due to one of the following:

  • Invalid or trial licenses present in the Floating License Manager.
  • Asset Link template version mismatch compared to the installed Asset Link version.
  • Older Asset Link templates present in the project, preventing proper license validation.

To verify template please follow below procedure,

Template_version_image_1

Version details:

Properties

Ensure the Asset Link template used in the project is compatible with the installed Asset Link version.

Use the following table for reference:

Asset Link Version

Template Version ($aEsxCEAssetlink)

Asset link 4.0

6850

Asset link 4.0 SP1

7211

In case any version mismatch is observed on the setup machine, please navigate to the following path:

Path

Please import this library into your Galaxy project. Doing so ensures that the correct version of the template is installed and applied in your setup.

This procedure resolves the trial license issue.

This Issue is observed in EPE for ASP2023 version. But its applicable to all the versions of Ecostruxure Process Expert Aveva System Platform.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings