我们今天能为您提供什么帮助?

PME - How to find the source of data for a virtual meter using Vista

Issue

There is a need to find where data under a virtual source is being logged from.

Product Line

ION Enterprise 5.x

ION Enterprise 6.x

StruxureWare Power Monitoring 7.x

Power Monitoring Expert 7.x

Power Monitoring Expert 8.x

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

Vista

Resolution

1. Open Vista and go to File > New.

2. Click and drag a Data Log Viewer onto the diagram:

Data Log Viewer

3. Right-click on the Data Log Viewer.

4. Open the Query Server tab and make sure the QUERYSERVER is shown. If it's blank, select Custom Query Server > Edit Link and select it manually.

Link queryserver

5. Open the Query tab > Edit Query. Select the virtual source where the data is logged under, click Add, then Next.

Link virtual source

6. The name of the log and the source where the data is originally logged from is shown.

In the example below, it's logged in a Data Recorder Module called "Totals Log" in the VIP.DEFAULT.

Identify original source and name of log

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings