How to Identify the Correct Device Type for Micrologic Trip Unit

Issue:

Sometimes when connecting a Micrologic Trip Unit to a system such as, Power Monitoring Expert (PME), it can present an error message "Translator Failure" or not show the proper values. This may be an indication that the incorrect device type is being used for this device in the program. To verify if this is the case, the device type for the unit can be identified by reading a specific Modbus register.


Product Line:
Micrologic A

Micrologic E

Micrologic P

Micrologic H

Environment:
Modbus Reading Program

Resolution:

To do this process, you will need a tool that can read Modbus registers. If you do not have a preferred program for this action, you can download the attached Modbus Tester program from this article Video: What is Modbus Tester and how do I use it? | Schneider Electric USA.

In order to figure out which trip unit product is being used, we will need to identify which Modbus register will return the proper code. On pg. 136 of the user guide found in the link and attached to the article, What are the Modbus registers for Micrologic A, P, and H trip units used in Powerpact P, R, and Masterpact NW/NT breakers? | Schneider Electric USA, under the "Product Identification" section it shows the register to read to get the device type returned to you for identification.

In the screenshot below, when you read Holding Register (R03 / W16): 8716 (full register value being 408716) it will return the type of the trip unit. Based on the number returned you will be able to identify if it is one of the trip unit types below Micrologic A, Micrologic E, Micrologic P, or Micrologic H.

product identification

施耐德電機Taiwan

附件
All A, P, H Registers (1).pdf [9.51 MB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings