Why is the Network Web Command Line Interface (CLI) grayed out?

Issue:

Why is the Network Web Command Line Interface (CLI) grayed out?

This image shows the Network Web Command Line Interface (CLI) is grayed out.

Product Line:

Network Management Card 2 (NMC2) - AP9630/AP9631 version 6.x.x above

  • Devices with an embedded Network Management Card 2 include (but are not limited to): Early model 2G Metered/Switched Rack PDUs (AP78, AP79, AP84, AP86, AP88, AP89), Rack Automatic Transfer Switches (AP44XX), Certain Audio/Video Network Management Enabled products, Early model Smart-UPS Online (SRT).

Network Management Card 3 (NMC3) - AP9640/AP9641 version 1.x.x.x above

  • Devices with an embedded Network Management Card 3 include (but are not limited to): Metered/Switched Rack PDUs (AP78, AP79, AP84, AP86, AP88, AP89, APDU9), Rack Automatic Transfer Switches (AP44A), Smart-UPS Online (SRT), SRTL2K-3K, Smart-UPS Modular Ultra 5kva to 20kva.

Network Management Card 3 (NMC3) - AP9544, AP9547

Environment:

All serial numbers

Cause:

The Network Web Command Line Interface (CLI) is grayed out when the Network Management Card already has an active SSH, Telnet, or Network CLI session. In this state, the card cannot accept an additional CLI connection until the existing session is disconnected.

Resolution:

The Network Management Card supports up to five (5) active combined SSH, Telnet, and Network CLI sessions. If the maximum number of sessions has been reached, or if a session becomes stuck, the Network Web CLI may appear grayed out.

To clear active or stuck user sessions, you will need to connect directly to the Network Management Card. Please follow the steps on FAQ000283784 to terminate the session(s) and restore access.

Should there be any other questions and/or concerns, feel free to reach out to us at 1-800-800-4272 or via chat with our technical support group at APC by Schneider Electric Customer Technical Support

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings