我们今天能为您提供什么帮助?

RemoteConnect x70 Logic Editor Does Not Retain Custom Logic Editor Color Settings

Issue

When using the x70 Logic Editor in RemoteConnect with a SCADAPack 474i, customized logic editor color settings may not behave as expected.

The following behavior may be observed after changing the color settings:

  • The page background changes to black, making the logic difficult to read.
  • Customized color settings are not retained.
  • The settings revert to their default values.

Environment

  • Product: SCADAPack 474i
  • Software: RemoteConnect
  • Component: x70 Logic Editor / Control Expert Logic Editor
  • Languages: FBD, ST, and LD
  • Configuration: Logic editor color settings in standard RGB format

Workaround

As a workaround, the required settings can be configured by directly modifying the applicable .ini file.

The following configuration files can be used depending on the programming language:

  • FBD (Function Block Diagram): FBDcolors.ini
  • ST (Structured Text): STColors.ini
  • LD (Ladder Diagram): LDColors.ini

Procedure

  • Close the Control Expert / x70 Logic Editor.

Location

  • Locate the applicable .ini file for the programming language being configured:
    • FBDcolors.ini for FBD
    • STColors.ini for ST
    • LDColors.ini for LD

Below is the image showing customization between Boolean TRUE and FALSE states for users

colors

  • Before making any changes, create a backup copy of the original .ini file and store it in a safe location. This allows the original configuration to be restored if required.
  • Open the applicable .ini file using a text editor such as Notepad++.
  • Modify the required color settings in the file.
  • Other configurable fields available within the applicable .ini file can also be modified using the same method, where required.
  • Save the modified .ini file.
  • Launch the Control Expert / x70 Logic Editor again.
  • Verify that the modified settings are applied as expected.

Important: Always take a backup of the original .ini file before modifying it. If the modified settings result in unexpected behavior, or if the original configuration is required again, restore the backed-up file.

Additional Information

The same approach can be extended to the different x70 Logic Editor programming languages by modifying their corresponding configuration files:

  • For FBD, modify FBDcolors.ini.
  • For Structured Text (ST), modify STColors.ini.
  • For Ladder Diagram (LD), modify LDColors.ini.

The settings available for modification depend on the fields present in each .ini file. Only existing configuration fields should be modified.

Resolution

Directly modifying the appropriate .ini file provides a workaround when color settings changed through the graphical interface are not retained or displayed correctly.

This method can also be used to modify other applicable configuration fields contained within the respective .ini files.

If necessary, the original settings can be restored using the backup copy created before making the changes.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings