PowerShelf PMC is showing a Yellow or Red Solid LED

Question:

PowerShelf PMC is showing a Yellow or Red Solid LED

Scenario:

The PMC LED may display solid yellow or solid red when the internal temperature measured at the PMC reaches the specified warning or critical temperature threshold.

The temperature used for this indication is measured by the temperature sensor located on the PMC board. Therefore, the PMC serves as the temperature source for this LED behavior.

Product Line:

SENVPS33KB2, SENVPS33KL-NP, SENVPS33KB3, SENVPMC002, SENVPMC003

Resolution:

PMC LED Behavior

  1. PMC LED Shows Solid YELLOW

    • Condition: Temperature Warning Threshold Reached
    • Temperature range: 60 °C < T < 70 °C or -25 °C < T < -5 °C
  2. PMC LED Shows Solid RED

    • Condition: Temperature Critical Threshold Reached
    • Temperature range: T > 70 °C or T < -25 °C


What temperature is being monitored?

The temperature indication is based on the internal temperature measured by the sensor located on the PMC board.

When the measured temperature reaches the warning threshold, the PMC LED turns solid yellow. When the measured temperature reaches the critical threshold, the PMC LED turns solid red.

Recommended Action : If the PMC LED indicates a temperature warning or critical condition, check and control the ambient temperature around the PowerShelf and verify the PMC temperature condition.

If the recommendations above does not resolve your concern or if you have any clarifications, please feel free to contact us at 1-800-800-4272 or chat with our technical support representatives.

施耐德電機Taiwan

探索更多
產品:
系列:
探索更多
產品:
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings