How to configure the Archive database connection between EAE and pgAdmin 4

Question

Why is EAE unable to communicate with the Archive database in pgAdmin 4?

Answer

Communication between EAE and the Archive database can fail if the database credentials or database owner are incorrectly configured.

To establish the connection, verify the following settings:

In EAE

Database credentials

  • The User ID and Password configured for the database connection in EAE must be identical to the credentials configured in pgAdmin 4.SQL image image2

Archive_Link configuration

  • In Archive_Link, verify the password configured for the database connection.
  • The Password must be the same as the password configured for the managementservice user.
  • With the default configuration, the credentials are:
    • User: managementservice
    • Password: managementserviceimage3 

      In pgAdmin 4

      1. Open pgAdmin 4.

      2. Locate the Program_Archive database.

      3. Right-click Program_Archive and select Properties.

      4. Under General, check the Owner field.

      5. Set the database owner to:

        postgres

        image4