To set up the drive to give speed control via the dial on the front:
Firstly make sure that the drive is in REMOTE Configuration mode i.e. the three LED’s to the left of the display are not flashing in sequence.
If they are, to get back to REMOTE press the MODE button for 3 seconds and then follow the sequence below:
Firstly make sure that the drive is in REMOTE Configuration mode i.e. the three LED’s to the left of the display are not flashing in sequence.
If they are, to get back to REMOTE press the MODE button for 3 seconds and then follow the sequence below:
- press the dial Go to Configuration Mode CONF press the dial.
- Go Down to Reference channel 1 (Fr1) press the center of the JOG DIAL (ENTER)
- Then set the FR1 to A1U1
- Press the escape button until rdY appears.
You can then run the drive by the run and stop buttons on the front of the drive with the speed on the dial.
To alter the speed in this mode Press the dial.
- Then press the center of the dial reF appears
- Press the center of the dial again 0.0 appears
- Then by rotating the dial the speed will increase (the display is a % (0-100%) not Hertz value of the difference between LSP and HSP)
If the start signal is to be given via a digital input LI* but the speed off the dial.
- go to the Full Menu (RDY >CONF>FULL)
- then to the Control Menu CtL- and press the center of the JOG DIAL (ENTER)
- Go to Channel Configuration (CHCF) and press the center of the JOG DIAL (ENTER)
- Then select the Separate mode (SEP) and then Command Channel 1 (Cd1) and enter
- Make sure it is set to terminals (tEr)
- Once set Press the escape button until rdY appears.
- Start the drive via the start button wires to the logic input.
- Then press the center of the dial, reF appears
- Press the center of the dial again 0.0 appears
- Then by rotating the dial the speed will increase (the display is a % of the difference between LSP and HSP)
This setting will remain active until the supply is removed to get back to it just repeat the pressing of the dial.
To monitor the Frequency or anything else go to reference mode.
Released for: Schneider Electric UK