Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What derating factors are applied to Tesys K, D, G contactors at altitude?

For contactors in the TeSys ranges (K, D & G) Please apply the following:

No derating below 3000m altitude for voltage and current in the power poles of the contactors.

Derating table for Tesys D contactors

For example, a LC1D80 at 5000m :

  • The maximum rated operational voltage is 1000V (IEC 947-4) and 690V (UL/CSA). At 5000m it becomes 1000V x 0.6 = 600V (IEC 947-4) and 690V x 0.6 = 414V (UL/CSA).
  • The maximum rated operational AC3 current is 80A at 5000m becomes 80A x 0.86 = 68A.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings