Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the recommended interval between tests for an RCBO?

The IEC 61008 and IEC 61009 series of product standards require such devices to be fitted with a test button (marked "T") on the front panel. The user can therefore check and be certain that the device is working correctly.

BS-7671 wiring regulations currently state 6 month intervals for pressing the test button.

Our global recommendation regarding testing of an RCD by pressing the test button is to consider the environmental conditions (we recommend a monthly test in harsh environmental conditions) and to follow the local regulations or guidelines on electrical installation inspection and maintenance.

Except for voltage dependent RCDs for which we recommend that the test be carried out:

-       after initial connection and any successive reconnection

- every month, whatever the environmental conditions or exposition to voltage surges

This monthly testing requirement is specific to devices like iC60H RCBO which are voltage dependent technology based.

For reference you may refer to the guide CA908066E page 42:

https://www.se.com/uk/en/download/document/CA908066E/

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings