Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to turn off the input phase loss in an ATV61 when using single phase?
Issue:
ATV61 Phase loss deactivate

Product Line:
All

Environment:
All

Cause:
Supply voltage single phase

Resolution:
To disable Input phase loss
Under the Main Menu
Go to the Drive Menu enter
Go to the Fault Management Menu 1.8  enter
Go to the "Input Phase Loss" parameter enter
Set "Input Phase Loss" to no (off)

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings