{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
What is a bPF fault on the ATS22 soft starter?

Issue:
bPF fault on the ATS22.

Product Line:
Altistart ATS22

Environment:
All

Cause:
Bypass contactor detected fault

Resolution:
Do a static test on the ATS22;
https://www.se.com/us/en/faqs/FA221890/
If test results indicate a shorted SCR or welded/stuck shorting contactor, replace the soft starter.
Reference the ATS22 installation guide (BBV51330)

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: