How can we help you today?
What is the derating factor used when sizing LH4N for a high number of starts per hour than the standard spec of 360 seconds.
Goals and Symptoms
What is the derating factor used when sizing LH4N for a high number of starts per hour than the standard spec of 360 seconds.
Facts and Changes
LH4N Starts/hour
starting
Causes and Fixes
There is not studies which gives a factor to determine the power of LH4 in an application with high number start/stop per hour upper her electrical characteristics of the product.
The catalogue tell you :
-'' if starting and stopping conditions are severe, or if the starting current must be controlled, it is preferable to use an ATS48 unit''.
- ''beyond this starting duty, the start unit must be derated by one size''.
However , we thinks when the number of start/stop is considerable and it would have been preferable to use a variable speed drive.
Note: The LH4 softstart family is obsolete. It was replaced by the ATS01 softstart, or in the case of the larger LH4's the ATS22.
Legacy KB System (APS) Data: RESL160232 V1.0, Originally authored by on , Last Edited by on
Related ranges: LH7, LH4
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.