Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is a dataset in SFT850?

A dataset is a collection of Data Attributes (DAs) grouped together to increase communication efficiency. They are used for reports and Goose messaging. By default there are 2 datasets predefined in the ICD file:
1. StDs dataset includes all status indications provided by all the protection logical nodes present in the Sepam, the switchgear logical nodes, the sensor and monitoring logical nodes and the physical device itself.
2. MxDs dataset includes all measurements values provided by all the measurement logical nodes present in the Sepam

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings