Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Modbus Broadcast report

Goals and Symptoms

Successful broadcast request on modbus on Premium/Micro PLC (SCP111/114 or SCY) returns 16#00FF as result in second word of management table (instead of 16#0000 for a correct exchange in other protocols)
Successful broadcast request on modbus on M340 PLC returns 16#0001 as result in second word of management table (instead of 16#0000 for a correct exchange in other protocols)

Causes and Fixes

To take into account when performing broadcast over Premium/Micro and M340.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings