Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can we upload programs with Vijeo Designer from the Magelis XBTG/GK/GT, HMIGK/GTO/GTU, HMISTO/STU?

Goals and Symptoms

Can we upload programs with Vijeo Designer from the Magelis XBTG/GK/GT, HMIGK/GTO/GTU, HMISTO/STU?

Causes and Fixes


It is necessary to previously configure the Vijeo-Designer project according to: In the Target's properties, for XBTG/GK/GT, HMIGK/GTO/GTU, HMISTO/STU...
- select download File System
- enable the Include Editor Project in the Download property.
In other words: if the project has not been downloaded with this option, you cannot upload it.


Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings