Product Line
Powerlogic and ION meters
Environment
Powerlogic
ION
Resolution
The withstand insulation test voltage for optical isolation for the meters are:
6200: 4330 Vrms
73xx: 4330 Vrms
75xx/76xx: 3750 Vrms
7700: 2500 Vrms
8500/8400/8300: 5303 Vrms
8600: 3750 Vrms
8800: 3750 Vrms
Released for: Schneider Electric UK









