Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What could cause all of the Modbus port lights to flash rapidly on my BM85C bridge mux?

Issue:

What could cause all of the Modbus port lights to flash rapidly on my BM85C bridge mux?

Product Line:

BM85C bridge mux, Modicon

Resolution:

If all of the Modbus port LED's are rapidly flashing simultaneously, check to see if
configuration port dip switches are correctly set. The bridge comes with all the
configuration port switch settings down, the BM85C requires the right/ upper switch to
have switch 8 in the up position. The configuration port switches are recessed and
easy to overlook.

switch positions

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings