Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What are the default format link parameters for Modbus communication with SoMove?
Issue:
Modbus format parameters

Product Line:
ATS48, ATV32, ATS22, ATV12, ATV212, ATV61, ATV71, ATV31, ATV312

Environment:
All models and serial numbers

Cause:
None

Resolution:
Parity = Even, Stop Bits = 1, Baud rate = 19200. Please note: The ATS48 has no parity as the default value. You must either change the format in the ATS48 to 8E1 or change the parity in SoMove to 8n1.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings