{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Event Notification Module custom message field [ACTIVETIME] does not return the correct year.
Event Notification Module custom message field [ACTIVETIME] does not return the correct year.

In the Delivery Relays setup of ENM the user is able to setup custom messages using OPC Fields.

IF you use the field [ACTIVETIME] there is an issue where it adds 1600 to the year.

As a work around, during setup make sure you denote the full format you want the Active Time displayed as.

Example:
[ACTIVETIME: MM/dd/yyyy]

MM for month
dd for day
yyyy for year

Make sure you get the capitalization correct.

Using this full format will get the correct year.

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.