Which bistable (latching) relay can replace a CA2DK122 contactor relay?

Part numbers CA2DK122, CA2DK22 and CA3DK22 referred to latching contactor relays in the old contactor relay range, which have now been replaced.

They consisted of two N/C contacts and two N/O contacts and two coils, A and E. When A is pulsed the contactor closes, then a second pulse onto E will open the contactor.

There is no direct substitution, but there is a complementary solution using CAD control relays which involves combining two products; a control relay CAD32xx and a latch block LAD6Kxx
(where xx is the control voltage code)

A pulse on the contactor coil terminals A1 and A2 causes the contactor to close.
Mechanical latching of the LAD6Kxx keeps the contactor closed.
A pulse on the coil of the LAD6Kxx, terminals E1 and E2, opens the contactor.
The duration of the control pulse on the mechanical latch block and the contactor must be:

>= 100 ms for AC control
>= 200 ms for DC control

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings